Chapter 1. VBOB Site Preparation and Specifications

The VBOB is shipped as a table-top unit but it can also be rackmounted.

See Chapter 2, “Rackmounting and Hardware Overview” for information on mounting a VBOB chassis in an SGI 3000 series rack.

Site Preparation

Table 1-1 provides site preparation information for a single VBOB chassis.

Table 1-1. Cooling and Power Requirements

Specification

Value Per Server

Cooling requirements

256 Btu/hour

Power consumption

75 W maximum

AC input to power supply

100-120/200-240 VAC at 50-60 Hz, 2/1A (autoranging)

Inrush current

35 A maximum

Nominal current draw

1.1 A @ 100-120 VAC, 0.6 A @ 200-240 VAC

UPS volt-amp rating

250 VA

As shown in Figure 1-1, the airflow in the chassis flows through the mesh grill at the front of the chassis, through the power supply enclosure, and over the motherboard. The hot air exhausts out of the back of the chassis.


Caution: Always keep at least 4 inches (10.2 cm) of clearance at the back of the chassis for cooling.

Figure 1-1. Chassis Airflow Diagram

Chassis Airflow Diagram

Technical Specifications

Table 1-2 lists physical and environmental specifications.

Table 1-2. Physical and Environmental Specifications

Specification

Value Per VBOB

Chassis dimensions

3.5 in. height (2U) x 17.5 in. width x 21.0 in. length (8.9 cm height [2U] x 44.4 cm width x 53.3 cm length) [Length includes rear BNCs]

Weight ( installed)

20 lb (16.4 kg) maximum

Installation orientation

Any, with 4 in. (10.2 cm) clearance at back

Acoustic noise

43 dBA approximate

Air temperature
Operating
Non-operating


+41 to +95 °F (+5 to +35 °C), up to 5,000 ft altitude
-40 to +149 °F (-40 to +65 °C)

Thermal gradient
Operating
Non-operating


18 °F (10 °C) per hour (maximum)
108 °F (60 °C) per hour (maximum)

Altitude
Operating

Non-operating


10,000 ft (3,048 m) MSL (maximum), derated 1 °C per 1,000 ft above
5,000 ft altitude (i.e. 30 °C temp at 10,000 ft)
40,000 ft (12,192 m) MSL (maximum)

Relative humidity
Operating
Non-operating


10% to 85%, noncondensing
5% to 95%, noncondensing

Mechanical shock
Operating
Non-operating


15 G, 3 ms (horizontal and vertical, half-sine wave)
30 G, 10 ms (horizontal and vertical, trapezoidal wave)

Mechanical vibration
Operating
Non-operating


0.25 G, 5-500 Hz, @ 1 oct/min
0.5 G, 3-300 Hz, @ 1 oct/min